Electrostatic Capacity Type Level Meter LIC-152 (2-line type)
Product Description
● Description
A electrostatic capacity / continuous direction type level meter is designed to meet the demand of spots and various applications . This meter checks the change of liquid level .
It is used in wide industrial fields such as observation wells that supervise and record the water level of hundreds m of underground, water supply ponds, river waterways and, a medical fluid tanks with high importance .
● Features
・Because of output display on a spot, direction can be confirmed immediately .
・Isolator is incorporated .
・Since the arrester is incorporated, it has high thunder resistance .
・Dual line permits long distance transmission
・It can be set where has no power supply .
・Output display can be selected m and %, direction confirmation according to applications can be served .
・It has high corrosion resistance
A electrostatic capacity / continuous direction type level meter is designed to meet the demand of spots and various applications . This meter checks the change of liquid level .
It is used in wide industrial fields such as observation wells that supervise and record the water level of hundreds m of underground, water supply ponds, river waterways and, a medical fluid tanks with high importance .
● Features
・Because of output display on a spot, direction can be confirmed immediately .
・Isolator is incorporated .
・Since the arrester is incorporated, it has high thunder resistance .
・Dual line permits long distance transmission
・It can be set where has no power supply .
・Output display can be selected m and %, direction confirmation according to applications can be served .
・It has high corrosion resistance
Standard Specifications
● Specifications (Power converter PS-205)
● Specifications (Transmitter LIC-152)
Power Supply | AC100/110 200/220V 50/60Hz |
Output Signal | DC4~20mA (Electrode line : having isolation between transmitters output) |
Maximum Line Resistance | 1〔PS-205 from output signal line〕 750Ω 2〔between LIC-152 to PS-205〕 500Ω (go and back + direction from transmitter side) |
Cable | CVVS 2C (CVV 2C close distance) |
Power Consumption | max 6VA |
Accuracy | Linearity : ±0.5% (FS) Repeatability : ±0.1% (FS) Power supply varying ±0.3% (FS) (power supply varying ±10%) |
Ambient Temperature | -15~+55℃ |
Ambient Humidity | 10~95% |
Body Structure | In board storage type Polycarbonate (black) |
Weight | about 600g |
Water-Proof Grade | IP-40 |
● Specifications (Transmitter LIC-152)
Operation Power Supply | DC15~26V |
Capable Load Resistance | 500Ω (DC24V) |
Output Signal | DC4~20mA or DC20~4mA U・D change switch incorporated |
Accuracy | ±0.5%FS |
Humidity | 10~95% (must not dewing) |
Ambient Temperature | -10~+60℃ |
Water-Proof Grade | IP-54 |